Part Number : MFAG0896-5
Alternate P/N : MFAG08965
NSN : 5925-00-728-1969 (5925007281969)
Item Name : Circuit Breaker
Manufacturer : Schneider Canada Inc
CAGE Code : 09710
NIIN : 007281969
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-728-1969 Item Description: Circuit Breaker | 5925 | 007281969 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Mfag0896-5 | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 3.000 INCHES NOMINAL |
ADAT | BODY WIDTH | 2.250 INCHES NOMINAL |
ADAU | BODY HEIGHT | 2.750 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.735 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 TERMINAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 15.000 NOMINAL AT 200 PCT ALL LOCATIONS AND 4.000 NOMINAL AT 300 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 3 CLIP AND 3 SCREW |
AJEC | BOSS HEIGHT | 0.156 INCHES NOMINAL |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
Low Price Warrantied inventory at competitive prices
Find it fast Search the world's largest inventory of electronic components by manufacturer, category or part number
Quality guaranteed We sell only warrantied and traceable parts
Get it fast All inventory ready to ship from our sellers
“We Proudly Support Intrepid Fallen Heroes Fund that serves United States Military Personal experiencing the Invisible Wounds of War : Traumatic Brain Injury (TBI) and Post Traumatic Stress (PTS). Please visit website (www.fallenheroesfund.org) and help in their valiant effort”.
Remember Us the Next Time If You are Looking for Aircraft Parts.
Request for Quote